Click here to get a full notes
Air Cond: Psychrometric
Dry air – essentially mixture of nitrogen, oxygen and traces of argon, carbon dioxide, neon etc.
Water vapour – which exists at low partial pressure. At low low atmospheric pressure and temperature, water vapour can be treated as ideal gas.
Assumptions.
(1) vapour contains no dissolved gases
(2) gaseous phases can be treated as ideal gas
(3) no interaction between components and all components are at the mixture temperature
Psychrometric properties All properties are based on the “dry-air part”. Consider a volume of moist air
Barometric pressure = 101.325 kPa Gibbs phase rule, F = 2 + 2 – 1 = 3 (ie need 3 intensive properties to define the state). Since pressure is fixed, need 2 other properties:(a) dry bulb temperature, TDB …………… easily measured
(b) moisture content, w
(c) dew point temperature, TDP
(d) percentage saturation,
(e) relative humidity,
(f) specific enthalpy, h
(g) specific volume, v
(h) wet bulb temperature, TWB ……….…….usually measured
Click here to get a full notes.
Click here for a psychrometric chart
Air Cond: Gas Mixture inside air cond system
(b) Mixture – each constituent retains its own identity; can be separated by mechanical means. Constituents in a mixture are called the components. Each component may exist in one or more phases.
Example of mixture:
2 components (air and water)
3 phases (gas, liquid and solid)
Click Mixture to read more
Air Cond system
Air Conditioning (AC) System
AC systems can be classified by the methods of achieving the within-the-space cooling (and heating):
1.1 Unitary unit
It is a compact, self-contained unit located within or next to the air-conditined space. Such a system includes the direct expansion (DX) system.
1.2 Split Unit
It is also a compact, self-contained DX system with the condensing unit (compressor and condenser) located at some distance from the evaporating unit (evaporator and expansion valve). Long refrigerant pipings connect the condensing and evaporating unit.
1.3 Central Systems
Central systems include: all-water system, all-air system and air-water system.
1.3.1 All-water system
In this system, a cooling medium (chilled water or brine – but not refrigerant) is supplied from a remote source and circulated through the terminal unit within the conditioned space.
1.3.2 All-air system
In an all-air system, the final cooling medium (air) is brought into the conditioned space through ducts and distributed within the space through outlets.
1.3.3 Air-water system
Such a system uses chilled water and cold air from a central station. The major part of thermal load is met by chilled water which is circulated through a coil.
1.4 All-air central centralised systems
1.4.1 Constant air volume (CAV) system
In a CAV system, the volume flow rate of air is constant. During part-load operation (eg on rainy days), terminal reheaters can be used to increase the supply air temperature to ensure conditioned space air dry bulb temperature is maintained at comfort level. Without reheat, indoor air temperature cannot be controlled when zone sensible loads are lower than design-day values; resulting in uncomfortable conditions.
1.4.2 Variable air Volume (VAV) system
In a VAV system, the volume flow rate of air is varied to ensure comfortabale indoor air dry bulb temperatures. An indoor air thermostat senses indoor air temperature variation and sends a signal to a VAV box control unit which increases the volume flow rate of supply air when the sensible load increases and vice-versa.
1.4.3 Dual-Duct/Multizone (DDMZ) system
In this system, the supply air temperature is varied to meet changing zone sensible loads. When zone sensible load decreases, zone air temperature will decrease and the indoor air thermostat sends a signal to the mix box damper to mix more bypassed air with less cool air, such that the higher supply air temperature will ensure that the indoor air temperature will rise to the set point value.
In the system, the supply air temperature is variable, but the volume flow rate of supply air is constant.
In dual-duct system, the mixing is done at the terminal unit, while in multizone system the mixing is accomplished at the air handling unit (AHU).
Air cond : Aircrafts Refrigeration
Gas cycle refrigeration
(i) Small amount of leakages are tolerable since air is the refrigerant.
(ii) The simplest open system requires only one heat exchanger
(iii) Readily available refrigerant
(iv) Cabin pressurization and air-conditioning can be combined into one operation
(v) Initial compression of the air is obtained by the ram effect (conversion of the high kinetic energy of ambient air relative to aircraft into enthalpy and ultimately pressure rise). Refrigerated air capacity ranges from 3 to 70 kg a minute.
Air cond: Vapor absorption type
Air cond: Sample Test with solution (Standard and actual cycle)
Air Cond: Past Year Final Exam Question
1. Air Conditioning Basic Cycle
a. T-s & P-h diagram
b. Using R-134a or R-12 table to find value of enthalpy h.
c. Find the work of compressor and refrigerating effect.
2. Sling psychrometer to find the value of the dry bulb and wet bulb with the specific value of
atmospheric pressure. This question want you to evaluate:
a. Partial Pressure
i. Water Vapor
ii. Dry air
b. Relative humidity
c. Humidity ratio
d. Specific enthalpy
3. Room design question. Using Psychrometric Chart to evaluate the value of
a. Outdoor air mass flowrate
b. Supply air
i. Dry bulb temperature
ii. Mass flowrate
c. mix air
i. Dry bulb temperature
ii. relative humudity
d. cooling coil load
4. Ducting design. To approximate tho total pressure drop inside the ducting.
click Air Condition to get a dual language question
Click Answer to get a solution
Air Cond: Type of Refrigerants
1. Inorganics refrigerants

2. Organics refrigerants

Click here to get a full notes
Air Cond: Basics concept of Air cond cycle
The basic concept of the air cond cycle using T-S diagram and P-H diagram.Air conditioning cycle is reverse carnot cycle.
More Detail of these notes & Example please click here!!
Refrigeration & Air Cond: Exercise Psychrometric Chart

These file contents of the exercise for the psychrometric
chart. Dry bulb and wet bulb temperature is given with atmospheric Pressure. for the full exercise question please click here!
Air Cond: Psychrometric chart

Sample Plotting of the Psychrometric chart. From the value of the Sensible heat factor (SHF) = 0.7, room design is 24 degree C and Humidity 50%. The outside air temperature is 31.3 degree C and Humidity is 70%. The Supply air, Apparatus Dewpoint, Mix air temperature, Outside air volume, supply air temperature, mix air volume, room air humidity, cooling bypass factor and etc can be evaluated through psychrometric chart.
Click here to get a Chart